Lightning protection solution related products

Protector for power supply

IEC61643-1 specification

Surge protector with the performance of direct lightning surge 10/350μs and induced lightning surge 8/20μs.


MZG-200 type

Enlarge

Protect power supply circuit up to AC200V from lightning surge.
ClassⅠ,ClassⅡ
[Dimension] W35 x D100 x H64
●Direct lightning strike(10/350μs・50kA)
●JIS standards(C5381-1)
●Applicable to DIN rail(35mm)

Main performance
item performance
test class JISC5381-1 classⅠ+ classⅡ
maximum continuous operating voltage Uc 230VAC
impulse current Iimp 10/350μs 50kA
nominal discharge current In 8/20μs 20kA
voltage protection level Up 1.5kV
dynamic current interrupting rating Ifi 3kA
wire AWG10~4(cross section area 5.5~22m㎡)
MZS-200AV type

Enlarge

Protect power supply circuit up to AC200V from lightning surge.
ClassⅠ,ClassⅡ
[Dimension] W35×D125×H64
●direct lightning strike (10/350μs・25kA)
●JIS standards (C5381-1)
●attachable to DIN rail (35mm)
●deterioraltion display

Main performance
item performance
test class JISC5381-1 classⅠ+classⅡ
maximum continous operating voltageUc 230VAC
impulse current Iimp 10/350μs 25kA
nominal discharge current In 8/20μs 20kA
voltage protection levelUp 1.5kV
dynamic current interrupting rating Ifi 50kA
wire AWG10~4(corss-section area 5.5~22m㎡)
MZG-NPE type

Enlarge

Protect power supply circuit up to AC 200V from lightning surge.
ClassⅠ,ClassⅡ
[Dimension] W70×D100×H65
●direct lightning strike (10/350μs・100kA)
●JIS standards (C5381-1)
●attachable to DIN rail (35mm)

Main performance
item performance
test class JISC5381-1 class Ⅰ
maximum continous operating voltage Uc 230VAC(N-PE)
impulse current Iimp 10/350μs 100kA
nominal discharge current In 8/20μs 20kA
voltage protection level Up 1.5kV
dynamic current interupting rating Ifi -
wire AWG10~4(cross-section area 5.5~22m㎡)
MZ-200 type

Enlarge

Protect power supply circuit up to AC200V from lightning surge, with deterioration function and alarm contact.

Class Ⅱ
[Dimension] 
plug part

+

jack part
MZ-200JK1 W18×D98×H66
MZ-200JK2
MZ-200JK1ARR
W36×D98×H66
MZ-200JK3
MZ-200JK2ARR
W54×D98×H66
MZ-200JK4
MZ-200JK3ARR
W72×D98×H66
●induced lightning surge (8/20μs・40kA)
●JIS standards(C5381-1)
●deterioration display function
●attachable to DIN rail (35mm)

Main performance
item MZ-100 MZ-200 MZ-ARR
test class JISC5381-1 class Ⅱ class Ⅱ class Ⅱ
maximum continuous operating voltage Uc 130VAC 255VAC 255VAC(N-PE)
impulse current Imax 8/20μs 40kA 40kA 75kA
nominal discharge current In 8/20μs 5kA 20kA 20kA
voltage protection level Up 0.7kV 1.4kV 1.0kV
failure display function plug part normal=blue
abnormal=red
normal=blue
abnormal=red
no/td>
warning function in failure jack part -
electric wire jack aprt AWG14~8(cross-section area 1.6~8m㎡)


※MZ-( )ARR is used when it is used to power supply point of MCCB or ELCB.
AV-201 type

Enlarge

Plug-in type protector for power supply.
[Dimension] W84×D23×H64
Main performance
item performance
maximum continuous
operating voltage
AC240V
impulse
protection level
≦1.5kV
(1.2/50μs、10kV impressed)
impulse discharge current 8/20μs、20kA、twice
VV-201 type

Enlarge

Protect from lightning surge which occur between lines of power supply with LED deterioration display.
[Dimension] W84×D23×H64
Main performance
item performance
maximum circuit voltage AC230V、DC300V
voltage limit less than 550V
at 8/20μs 1kA (after 5μs)
impulse discharge current 10,000A at 8/20μs
1,000A at 10/200μs
insulated resistance (from terminal to board) more than 100MΩ at DC500V
dielectric strength (from terminal to board) AC3kV one minute
LED display noramal green color 2 lighting
deterioration, failure green color 1 light-out, 2 lights-out
RP-100 type, RP-200 type

Enlarge

Protect from lightning surge which occurs in lines of power supply.
[Dimension] W65×D50×H50
Main performance
item RP-100 type RP-200 type
maximum continuous
operating voltage
AC120V AC240V
impulse
protection level
≦1kV
(1.2/50μs、3kV impressed)
impulse discharge current 8/20μs、20kA
AV-11, AV-13, AV-14 type

Enlarge

Protect power supply circuit with alternative current of ≦125V, 240V and 440V respectively from lightning surge.
[Dimension] AV-11type: W17×D10×H50
        AV-13 type: W19×D11×H52
        AV-14 type: W20×D13×H52
Main performance
item AV-11 type AV-13 type AV-14 type
maximum continuous
opearating voltage
AC125V AC240V AC440V
impulse
protection level
800V 1.200V 2.000V
(10/200μs、3kV)
impulse
discharge current
8/20μs、4.5kA
AV3P-1 type, AV3P-2 type

Enlarge

Protect power supply circuit below alternate current of ≦125V and ≦240V respectively from lightning surge.
[Dimension] AV3P-1 Type:W22×D19×H40
        AV3P-2 Type:W25×D19×H40
Main performance
項目 AV3P-1 type AV3P-2 type
maximum continuous operating voltage AC125V AC240V
impulse protection level 800V 1.200kV
(10/200μs、3kV)
impulse discharge current 8/20μs、9kA
S480-S type

Enlarge

Protect power supply circuit up to AC480V from lightning surge.
[Dimension] W105×D60×H65
Main performance
item perforamnce
maximum continuous operating voltage AC550V
impulse protection level 10/200μs・3kV impressed
≦2kV
impulse discharge current 8/20μs・20kA
10/200μs・2500A
Lightning protection transformer ST type

Enlarge

Best suitable for lightning protection of power supply.
Main performance
item specification
input-output voltage AC100V、AC200V、AC400V、AC100/200V
wire connection(number of phase) single-phase(two-wire, three-wire), three-phase three-wire(delta connection)
capacity single-phase 0.5~30kVA
three-phase 1~75kVA
working frequency 50Hz/60Hz
insulated resistance more than 100MΩ at DC500V
withstand voltage between Input and output AC10kV (one minute)
impulse (1.2/50μs)30kV
between input and earth
between output and earth AC3kV (one minute)
voltage volatility and efficiency single-phase capacity less than 0.5kVA 1~2kVA 3kVA more than 5kVA
voltage volatility less than 5% less than 4% less than 3%
efficiency more than 93% more than 95%
three-phase capacity less than 7.5kVA more than 10kVA
voltage volatility less than 3% less than 2%
efficiency more than 95% more than 97%
insulation type single-phase A type less than 2kVA、B type more than 3kVA
three-phase A type less than 60kVA、B type more than 75kVA
temperature increase limit A type less than 55℃
B type less than 75℃
surge transition rate less than 1/1,000

※The above mentioned specifications are just an example. Various types of product can be manufactured accorfing to cutomers request.
Lightning protection transformer STC type

Enlarge

Best suitable for lightning protection of power supply with passing rate of below 0.1%.
Main performance
item specificaion
input-output voltage AC100V、AC200V、AC400V、AC100/200V
wire connection (number of phase) single-phase(two-wire, three-wire), three-phase three-wire(delta connection), three-phase(delta connection)
capacity single-phase 0.5~30kVA
three-phase 5~100kVA
working frequency 50Hz/60Hz
insulation resistance more than 100MΩ at DC500V
withstnand voltage > between input and output AC10kV (one minute)
impulse(1.2/50μs)30kV
between input and earth
beteen output and earth AC3kV (one minute)
voltage volality and efficiency single phase capacity less than 1kVA 2kVA more than 3kVA
voltage volatility less than 5% less than 4% less than 3%
efficasy more than 93% more than 95%
three phase capacity less than 7.5kVA 10~30kVA more than 40kVA
voltage volatility less than 4% less than 3% less than 3%
efficiency more than 94% more than 95% more than 96%
insulation type single phase B type
three phase B type
limit of temperature rise less than 75℃
surge transition rate less than 1/1,000

※The above mentioned specifications are just an example. Various types of the products can be manufactured according to customers request.
IT Thunder guard transformer

Enlarge

In advanced information society, IT related instrument is essential. The smaller/more compact IT instrument become, more fragile against lightning it become. IT thunder guard transformer will shut down the lightning surge flowing into IT instrument in 19 inch-rack.

characteristics
・protect IT instruments from lightning surge(impulse withstand voltage, surge transition rate less than 1/1000)
・attachable to 19-inch lack
・output plug is placed at back side, installed overcurrent protection breaker
・transformer capacity selectable among 0.5kVA・1kVA・2kVA・3kVA
・protector for power supply has deterioration warning LED
・easy exchange of protector module
Main performance
item specification
input-output voltage AC100V、200V (single phase)
capacity 0.5kVA・1kVA・2kVA・3kVA
working frequency 50Hz/60Hz
insulated resistance more than 100MΩ at DC500V
withstand voltage between input and output: AC10kV (one minute)、
impulse(1.2/50μs)30kV between input and earth: AC10kV (one minute)、
impulse(1.2/50μs)30kV between output and earth: AC3kV (one minute)
voltage volatility 0.5kVA 1~2kVA 3kVA
less than 5% less than 4% less than 3%
efficiency 0.5~2kVA more than 93%
3kVA more than 95%
surge transition rate more than 60dB (less than 1/1000)
color light beige
noise filter function 40dB(symmetric wave 1~10MHz)
weight 0.5kVA 1kVA 2kVA 3kVA
about 15kg about 22kg about 32kg about 38kg
※The above mentioned specifications are just an example.
Lightning protector Megasorb

Enlarge

Prevent from huge current lightning surge with high surge current withstand 8/20Ύs㎻100KA protector.
[Dimension] F type :W650×D520×H180
        H1 type:W650×D350×H180
Main performance
item F type H1 type
maximum circuit voltage AC220V/AC110V
impulse
protection level
MEGA ZORB ≦7kV
(1.2/50μs、50kV)
Strike Sorb ≦800V
(8/20μs、3kA)
impulse
current withstand
MEGA ZORB 10/350μs、60kA
8/20μs、100kA
Strike Sorb 8/20μs、200kA

Return to Top