Product Info

HOME > Product Info > Lightning protection solutions > Power supply SPD > MZCR-100,200,400 series

MZCR-100,200,400 series

 
MZCR-200 series  

Induced lightning protection

 

 

IEC 62305-4;2006 compliant

Class II (IEC 61643-1;1998) compliant

 
 

MZCR-100, MZCR-200 type

 

MZCR-100, MZCR-200 type

Zoom

 

This is a power supply SPD (Surge protective device) that provides lightning surge protection for power supply circuits up to AC255V. It is a plug-in type that enables the jack and main unit to be separated, and has excellent maintenance properties. It also comes equipped with a Device deterioration facility function and warning contact. The JK [ ] N type fits M4 round crimped terminals (width: up to 12mm).


Class II compliant
RoHS compliant

[Dimensions]
Plug + jack

MZCR-200JK1type

MZCR-200JK1Ntype

W18×D102×H64

MZCR-200JK2type
MZCR-200JK2Ntype

MZCR-200JK1ARRtype

MZCR-200JK1ARRNtype

W36×D102×H64

MZCR-200JK3type
MZCR-200JK3Ntype

MZCR-200JK2ARRtype

MZCR-200JK2ARRNtype

W54×D102×H64

MZCR-200JK4type
MZCR-200JK4Ntype

MZCR-200JK3ARRtype

MZCR-200JK3ARRNtype

W72×D102×H64
*MZCR-100 [ ]type has the same dimensions

Induced lighting (8/20μs,40kA) protection

IEC compliant(61643-1)

Equipped with Device deterioration facility and warning contacts

Can be attached to DIN rail (35mm)

Fits M4 round crimped terminals (width: up to 12mm). (JK [ ] N type )

Response speed 3ns or less

 
Main performance characteristics
 
Item

MZCR-100JK[ ]

MZCR-100JK[ ]

MZCR-200JK[ ]

MZCR-200JK[ ]

MZCR-200JK[ ] ARR MZCR-200JK[ ]ARR

Test class IEC 61643-1 ClassII ClassII ClassII
Maximum continuous operating voltage Uc   150VAC 255VAC 255VAC
Maximum discharge current Imax 8/20μs 40kA 40kA

40kA (each phase)

75kA (N-PE)

Nominal discharge current In 8/20μs 5kA 20kA 60kA
Voltage protection level Up   0.7kV 1.4kV 1.0kV
Device deterioration facility Plug section Normal operation: green
Faulty operation :red
Normal operation: green
Faulty operation :red
None
Defect warning contact function Jack section Yes Yes -
Applicable lines Jack section AWG14 to 8 (cross sectional area 1.6 to 8mm2)
*MZCR-( )ARR type is used when there is MCCB or ELCB installed on the power supply side.
 
 
 

MZCR-400 type

 

MZCR-400 type

Zoom

 

This SPD is used for the protection of solar power generation systems and wind power generation systems from lightning surges on power supply circuits up to AC400V and DC700V. It is a plug-in type that enables the jack and main unit to be separated, and has excellent maintenance properties. It also comes equipped with a Device deterioration facility function and warning contact.
Class II compliant
RoHS compliant
Used in lightning countermeasures for solar power generation systems and wind power generation systems

[Dimensions]
Plug + jack MZCR-400JK1 W18×D102×H64
MZCR-400JK2 W36×D102×H64
MZCR-400JK3 W54×D102×H64
MZCR-400JK1ARR W36×D102×H64
MZCR-400JK2ARR W54×D102×H64
MZCR-400JK3ARR W72×D102×H64

Induced lighting (8/20μs,40kA) protection

IEC compliant(61643-1)

Equipped with Device deterioration facility and warning contacts

Can be attached to DIN rail (35mm)

Up to DC700V

 
 
Main performance characteristics
 
Item MZCR-400 MZCR-400ARR
Test class IEC 61643-1 Class II Class II
Maximum continuous operating voltage Uc   For AC500V
Maximum discharge current Imax 8/20μs 40kA 75kA
Nominal discharge current   In 8/20μs 20kA 60kA
Voltage protection level  Up   2.5kV 1.5kV
Device deterioration facility Plug section Normal operation: green
Faulty operation :red
-
Defect warning contact function Jack section Yes -
Wire Jack section AWG14 to 8 (cross sectional area 1.6 to 8mm2)
 
*MZCR-400JK[ ] ARR type is used when there is MCCB or ELCB installed on the power supply side.
 
 
 
 
 

PAGE TOP