Product Info

CLP type

 

CLP type

Zoom

 

Category C2, Category D1 compliant
This high withstand capacity SPD (surge protective device) for communication equipment provides protection against lighting surge current for communication lines, such as telephone lines and control lines, etc.
●IEC compliant (10/350μs)
●High withstand capacity (20kA)
●ADSL, TEL, ISDN
●Main unit and jack can be separated.
●Can be mounted on a DIN rail
RoHS compliant

【Dimensions】 W18×D104×H68

 
Main performance characteristics
 

※ "JKN" is a screw-terminal-connection type. The screw size is M3 and the applicable solderless terminal is less then 6.6mm.

 
Item

CLP-EN1JK

CLP-EN1JKN

CLP-EN3JK

CLP-EN3JKN

CLP-H3aJK

CLP-H3bJK

CLP-H3cJK

CLP-H3dJK

CLP-H3aJKN

CLP-H3bJKN

CLP-H3cJKN

CLP-H3dJKN

Application ADSL
ISDN
TEL
ISDN Instrumentation line
Slow pulse
Wind speed meter
DC4-20mA
DC10-50mA

Maximum continuous

operating voltage (Uc)

170VDC 52VDC H3a:9V
H3b:13.5V
H3c:27V
H3d:52V
Permissible circuit current 100mADC
Series resistance 5Ω±10%
Insertion loss 1.0dB or less
(DC to 10MHz)
1.0dB or less
(DC to 400kHz)

Voltage

protection level

(Up)

1kV/μs 400V or less 200V or less
1.2/50μs, 10kV H3a:40V or less
H3b:45V or less
H3c:60V or less
H3d:90V or less

Impulse current

(Imax)

8/20μs 20kA
10/350μs 5kA

Impulse durability

Category C2

(8/20μs)

10kA (10 times)

Category D1

(10/350μs)

5kA (2 times)

Operating environmental

conditions

Rated perating

temperature
Rated perating

humidity

-40℃ to +70℃
96% or lower (no condensation)
Wiring method Relay (〇), Hanging exposed (×)
 
All items comply with IEC 61643-21stipulations.
 
 
Item

CLP-K2JK

CLP-K2JKN

CLP-K3JK

CLP-VA65JK

CLP-VA65JKN

Application Control power supply
Relay line
Speaker line
Remote observation control device Control power supply

Maximum continuous

operating voltage (Uc)

180VDC 52VDC 65VDC
Permissible circuit current 3ADC 3ADC 1ADC
Series resistance
Insertion loss 1.0dB or less
(DC to 10MHz)
1.0dB or less
(DC to 1MHz)
1.0dB or less
(DC to 400kHz)

Voltage

protection

level

(Up)

1.2/50μs,

10kV

1300V or less

8/20μs,

2.5kV

330V or less (L-E)

330V or less (L-L)

Impulse

current

(Imax)

8/20μs 20kA

10kA (L-E)

5kA (L-L)

10/350μs 2kA

1kA (L-E)

0.5kA (L-L)

Impulse

durability 

Category C2

(8/20μs)

4kA (10 times) 10kA (10 times)

Category D1

(10/350μs)

2kA (2 times) 1kA (2 times)

 Operating environmental

conditions

 Rated operating temperature
Rated operating

humidity

-40℃ to +70℃
96% or lower (no condensation)

 Wiring method 

Relay (〇), Hanging exposed (〇)
 
All items comply with IEC 61643-21stipulations.
 
 
Item

CLP-NMJK

CLP-NMJKN

CLP-N1JK

CLP-N1JKN

Application Balanced line
Multi-core measurement line
Wind speed meter
Platinum thermometer
Balanced line
Teleconference
Telemetry line
Thermocouple

Maximum continuous

operating voltage (Uc)

170VDC 52VDC
Permissible circuit current 3ADC
Series resistance
Insertion loss 1.0dB or less
(DC to 1MHz)

Voltage

protection

level

(Up)

1.2/50μs,

10kV

1000V or less (L-E)

50V or less (L-L)

900V or less

Impulse

current

(Imax)

8/20μs 20kA
10/350μs 5kA

Impulse

durability

Category C2

(8/20μs)

10kA (10 times)

Category D1

(10/350μs)

5kA (2 times)

Operating

environmental

conditions

Rated operating temperature
Rated operating

humidity

-40℃ to +70℃

96% or lower (no condensation)

Wiring method Relay (〇), Hanging exposed (×) Relay (〇), Hanging exposed (〇)
 
All items comply with IEC 61643-21stipulations.
 
 

PAGE TOP