| item |
specification |
| input-output voltage |
AC100V、AC200V、AC400V、AC100/200V |
| wire connection(number of phase) |
single-phase(two-wire, three-wire), three-phase three-wire(delta connection) |
| capacity |
single-phase |
0.5〜30kVA |
| three-phase |
5〜100kVA |
| working frequency |
50Hz/60Hz |
| insulated resistance |
more than 100MΩ at DC500V |
| withstand voltage |
between Input and output |
AC10kV (one minute) impulse (1.2/50μs)30kV |
| between input and earth |
| between output and earth |
AC3kV (one minute) |
| voltage volatility and efficiency |
single-phase |
capacity |
less than 1kVA |
2kVA |
more than 3kVA |
| voltage volatility |
less than 5% |
less than 4% |
less than 3% |
| efficiency |
more than 93% |
more than 95% |
| three-phase |
capacity |
less than 7.5kVA |
10〜30kVA |
more than 40kVA |
| voltage volatility |
less than 4% |
less than 3% |
less than 3% |
| efficiency |
more than 94% |
more than 95% |
more than 96% |
| insulation type |
single-phase |
B type |
| three-phase |
B type |
| temperature increase limit |
less than 75℃ |
| surge transition rate |
less than 1/1,000 |