Product Info

HOME > Product Info > Lightning protection solutions > Gas Tube Surge Arresters > Y type, Y08SV type arresters

Y type, Y08SV type arresters

 

Y type, Y08SV type arresters

 

·UL approved (UL1449, File No. E328370)
·2-electrode type
·Capacitance 1pF or less (IMHz)

RoHS compliant

[Dimensions] W4.3×φ6

 
 
Product characteristics
 
Type Y-152B Y-212B Y-302B Y-402B
DC sparkover voltage 1kV/s 1,500V±20% 2,100V±400V 3,000V±20% 4,000V±20%
Impulse sparkover voltage 100V/μs <=2,200V <=3,000V
(10/200μs)
<=4,000V <=5,000V
AC discharge current AC50Hz 1A, 1s 10times - 1A, 1s 10times 1A, 1s 10times
Impulse discharge current 8/20μ 10kA,1time
3kA,+5,-5times
1kA,2times 10kA,1time
1kA,+5,-5times
5kA, 1time
1kA,+5,-5times
Impulse life 10/1000μs 500A,10times 100A,100times
(8/20μs)
500A,10times 500A,10times
Insulation resistance >=10,000MΩ
(DC 500V)
>=10,000MΩ
(DC 500V)
>=10,000MΩ
(DC 1,000V)
>=10,000MΩ
(DC 1,000V)
 
Type Y08SV-272B
DC sparkover voltage 1kV/s 2,430〜3,000V
Impulse sparkover voltage 100V/μs <=3,900V
(1kV/μs)
AC discharge current AC50Hz -
Impulse discharge current 8/20μ 3kA
+10,-10times
Impulse life 10/1000μs 100A,300times
(8/20μs)
Insulation resistance >=100MΩ
(DC 1,000V)
 

*Use as UL approved products carries certain conditions. Please confirm beforehand.

 
 

PAGE TOP